TURN OFF POWER TO THE FIXTURES.
REMOVE LAMPS AND BALLAST COVER.
DISCONNECT BALLAST FROM POWER SUPPLY.
REMOVE AND DISCARD EXISTING SOCKET PLATE AND BALLAST IN
ACCORDANCE WITH LOCAL CODES AND REQUIREMENTS.
INSERT NEW LAMP HOLDERS INTO PROVIDED SOCKET PLATE.
INSTALL AND CONNECT NEW BALLAST (BY OTHERS) TO
LAMPHOLDERS PER DIAGRAM ON BALLAST LABEL.
SECURE SOCKET PLATES WITH "TEC" SCREWS SO THAT THE
LAMPHOLDERS ARE AGAINST THE ENDS OF THE FIXTURE AND CENTERED
LONGITUDINALLY
CONNECT BALLAST LEADS TO POWER SUPPLY ( ENSURE BALLAST IS
GROUNDED TO FIXTURE).
NOTE: IF THE INCOMING POWER IS END FED,
BEND CENTER TAB DOWN TO ALLOW ROOM FOR WIRES TO PASS.
SNAP R304 REFLECTOR INTO TABS LOCATED ON SOCKET PLATES.
CLEAN REFLECTOR, INSTALL LAMPS AND TURN ON POWER.